SF6 gas pressure reducing valve device and inflation pipeline
Model: Winfoss-A22
Pressure measurement range: 0-1.000MPa
Measurement accuracy: better than 0.2
Temperature measurement range: -35-100℃
Temperature measurement error: ≤±1.0℃
Working principle: built-in airbag, automatic pressurization by air cylinder method, no need for external air source
SF6 Density Relay Calibrator (Winfoss-A22)
Fully automatic, zero emission of SF6 gas in the whole process, healthy and environmentally friendly. Equipped with a full set of connectors corresponding to various switches at home and abroad, worry-free!
Overview
SF6 Density Relay Calibrator (Winfoss-A22) is an intelligent and fully automatic SF6 emission-free environment-friendly built-in airbag density relay calibration instrument. The instrument adopts single-cycle instruction microcomputer technology, and its running speed is 10 times that of ordinary single-chip microcomputer. It can perform on-site verification of SF6 density relays with pointer contact output and intelligent current output, and use interrupt mode to capture the action of density relays in real time. Therefore, the instrument measurement is more accurate and timely. This instrument is a portable calibration instrument that can standardize the pressure of SF6 gas at any ambient temperature. It can also calibrate SF6 density gauges and pressure gauges.
In a closed container, the pressure of SF6 gas at a certain temperature can represent the density of SF6 gas. It is customary to take the SF6 gas pressure at 20°C as the standard value. During on-site verification, under different ambient temperatures, the measured pressure value should be converted into its corresponding pressure value at 20°C to judge the performance of the SF6 density relay.
Winfoss-A22 emission-free environmental protection type SF6 density relay calibrator can complete the calibration process automatically, without any pollution to the environment, easy to use and accurate measurement, and the Chinese menu operation is simple and clear.
Features
- The instrument has a built-in capsule replacement chamber, and the calibration range covers the entire range of 0-1Mpa. The calibration process is smooth and can be completed in one go without interrupting the air supply in the middle. Zero emission of SF6 gas throughout the calibration process.
- The instrument has a built-in capsule replacement air chamber, which realizes static sealing instead of dynamic sealing and improves the sealing performance of the instrument.
- During the calibration process, the SF6 gas is internally circulated, and there is no emission to the atmosphere, which is more environmentally friendly and safer.
- The structure adopts double sealing design of hand valve and self-sealing valve, which is easy to operate and can prevent the pipeline from entering moisture and air. There is no SF6 emission and leakage before and after calibration.
- The air supply device has a simple structure and is easy to operate. Cleaning and supplemental gas can minimize the internal micro-water and impurity gas content.
- Can automatically identify normally open and normally closed density relays; can verify single signal (single alarm, single blocking), single alarm single blocking and single alarm double blocking density relays.
- Equipped with a full set of transition joints, the density relay of most types of switches can be checked online without disassembly.
Technical parameter
measurement accuracy: | Better than grade 0.2 |
Pressure display resolution: | 0.001MPa |
Pressure measurement range: | 0-1.000MPa |
Temperature measurement range: | -35-100℃ |
Temperature measurement error: | ≤±1.0℃ |
working principle: | Automatic pressurization by cylinder method, built-in air bag, no external air source required |
SF6 gas emissions | Zero emission of SF6 gas in all calibration processes |
Display method | 7-inch large industrial-grade high-definition color touch screen |
Operation method | Dual use of touch screen and physical buttons |
data storage | 100 sets of measurement data can be saved, and calibration data can be saved for life |
data printing | It comes with a high-speed micro thermal printer, and the verification result can be printed after the verification is completed. |
communication method | Built-in USB interface, easy to share data. |
Working power: | AC/DC dual-purpose AC/DC: 220V±10% 50Hz (built-in high-capacity lithium battery pack 24V 20Ah) |
Machine power consumption | <50W |
Check time: | The full-scale calibration time is ≤ 5min, and the air pressure adjustment process is gentle. |
Calibration principle
The pressure of the gas enclosed in the container changes with the change of temperature. In order to have a unified standard for comparison, we usually take the relative pressure value of 20 °C as the standard value. When the density table is calibrated, it is converted into the equivalent pressure value at 20 ℃ according to the corresponding relationship between pressure and temperature, and then compared.
Blocking recovery value verification:
- When the pointer of the SF6 density relay is zero, inflate the relay slowly and uniformly. When the SF6 density relay issues a latching action, record the pressure value at the ambient temperature at that time, and convert it into the equivalent pressure value at 20°C. This equivalent The pressure value is the latching recovery value of the SF6 density relay.
Alarm response value verification:
- Inflate the SF6 density relay slowly and uniformly. When the SF6 density relay issues an alarm action, record the pressure value at the ambient temperature at that time, and convert it into an equivalent pressure value at 20°C. This equivalent pressure value is the value of the SF6 density relay. Alarm reply value.
Overpressure recovery value verification:
- Inflate the SF6 density relay slowly and uniformly. When the SF6 density relay sends an overpressure signal, it starts to slowly and uniformly deflate the SF6 density relay. When the relay overpressure alarm signal is issued, record the pressure value at the ambient temperature at that time, and convert The equivalent pressure value at 20 ℃, this equivalent pressure value is the overpressure recovery value of the SF6 density relay.
Alarm value verification:
- At ambient temperature, when the pressure value in the SF6 density relay is higher than the alarm response value, it starts to deflate slowly at a constant speed. When the SF6 density relay sends out an alarm signal, record the pressure value at the ambient temperature at that time, and convert it to 20°C, etc. Effective pressure value, this equivalent pressure value is the alarm value of SF6 density relay.
Blocking value check:
- Deflate the SF6 density relay slowly and uniformly. When the SF6 density relay sends a blocking signal, record the pressure value at the ambient temperature at that time and convert it into an equivalent pressure value at 20°C. This equivalent pressure value is the SF6 density relay. the blocking value.
Overpressure value check:
- Inflate the SF6 density relay slowly and uniformly. When the SF6 density relay sends an overpressure signal, record the pressure value at the ambient temperature at that time and convert it into an equivalent pressure value at 20°C. This equivalent pressure value is the SF6 density relay. the overpressure value.
Product configuration
- Calibrator host: 1 set
- Connecting trachea with self-sealing at both ends: 1 piece
- Checkpoint sampling wire: 1 piece
- Temperature probe: 1 piece
- A full set of transition joints: 1 set
- Special toolbox: 1 piece
- Power cord: 1 piece
- Provide on-site training guidance and conduct on-site demonstration operations.
- Provide detailed Chinese manual and user guide.
- One year free warranty, lifetime spare parts support and maintenance.
- The hotline is available 365 days a day to answer user inquiries.