PRODUCTS
SF6 micro water density online monitoring system
Model: Winfoss-S6
Pressure range: 0.000MPa~1.000 Mpa
Pressure Accuracy: Class 1; Resolution: 0.001 Mpa
Dew point measurement: -80℃~20℃
Dew point accuracy: ±2℃; Resolution: 0.1℃
Temperature measurement: -30℃~85℃
SF6 Micro Water Density Online Monitoring System (WINFOSS-S6)
Original imported sensor, precise measurement, long life; patented sealing technology, zero leakage, effectively guarantee the safety of high-voltage electrical equipment!
Product description
According to "Q-GDW 534-2010 Technical Guidelines for Online Monitoring System of Substation Equipment", "DLT/1054-2007 Technical Supervision Regulations for Insulation of High Voltage Electrical Equipment", "QGDW 172-2008 Guidelines for Condition Maintenance of SF6 High Voltage Circuit Breakers", " DLT 846.5-2004 General Technical Conditions for High Voltage Test Equipment" Part 5: Sulfur Hexafluoride Trace Moisture Meter.
SF6 micro-water density online monitoring system (Winfoss-S6) adopts high-performance micro-water sensor and density sensor with temperature compensation function. Under the premise of not emitting SF6 gas, the long-term condition monitoring of SF6 circuit breakers is carried out to ensure the safe and stable operation of power equipment and to realize condition maintenance.
SF6 density micro-water online monitoring system (WINFOSS-S6) is a high-precision online humidity sensing technology introduced by Weavers, based on the original density monitoring, based on the high-quality management , Shenkai, Xikai and other high-voltage switch factories have cooperated in related technologies, and launched SF6 gas density and microelectronics technology, which integrates sensing detection technology, digital processing technology, data communication technology, database technology and other related power system information management technologies. Water online monitoring system. The core of which is a micro-water measurement and analysis algorithm based on the DRYCAP® detection technology. Analyze the results. It ensures that the trend change of the deterioration of the internal gas quality can be more accurately reflected through the change of the micro water content. So as to provide a numerical basis for users to make scientific decisions.
Pressure measuring transducer, which can be installed directly in pressure systems up to 50bar (725psia). In addition to the gas dew point temperature detection function, the sensor can also detect the gas pressure. Therefore, the sensor can directly detect the dew point temperature of the gas under pressure. The sensor is especially suitable for the detection of the micro-water content of SF6 gas and the detection of the density of SF6 gas in the power industry. Various parameters.
The SF6 micro-water density online monitoring device (WINFOSS-S6) is mainly used in the online monitoring of high-voltage electrical equipment using SF6 gas insulation in substations. The SF6 micro-water density online monitoring device can monitor the SF6 gas pressure, Density, temperature, dew point and PPM values. And provide SF6 gas moisture exceeded alarm function, density alarm. The data processing server automatically collects and stores monitoring data, and completely preserves the data trend (the data can be preserved for more than 15 years). The data processing server displays and processes the received data, and gives the test results and the change trend curve. The monitoring data and alarm signals can be uploaded to the upper-level monitoring center or the background of the fortune monitoring in real time.
Dew point measurement range: -50~+20℃
Temperature measurement range: -40~+60℃
Pressure measurement range (absolute pressure): 100 ~ 1200kPa
Dew point measurement accuracy: ±3℃td (for details, see measurement accuracy and measurement conditions under pressure)
Temperature measurement accuracy: 0~+50℃ ±0.5℃
-40~+80℃ ±1℃
Pressure measurement accuracy: 0~+50℃ ±0.5%
-40~+60℃±0.75%
Calculation parameters: gas pressure value (SF6 gas) at 20°C 100~1200kPa
The density of SF6 or SF6/N2 mixed gas is 0~100kg/m³
PPM micro water content calculated according to volume concentration 40~40000ppm
Dew point value converted to atmospheric pressure -65~+20℃
output:
Digital output: RS485 interface (isolated)
Digital output interface baud rate: 9600bps
Digital output protocol: modbus
Interface connector specification: relay socket connector
Use environment:
Temperature: -40~+60℃(-40~+140F)
Relative humidity: 0~95%RH
Pressure: 0~50bar a (725 psia)
Measured gas: non-corrosive gas
Working power supply: 18~28VDC
Working current: 25mA during normal measurement
70mA when high temperature heating and clearing
Shell material: stainless steel
Sensor protection cap: stainless steel hollow protection cap
Mechanical interface: G1/2
Protection class: IP65
Storage temperature range: -20~+80℃
The digital SF6 gas density and micro water comprehensive online monitoring and diagnosis system includes:
1. Distributed in the urban dispatch center or the remote client of any office desktop computer according to the user's needs (responsible for remote monitoring of the SF6 switch density and micro-water operation status in all substations within the jurisdiction), located in the power distribution cabinet of the main control building of the monitored substation The on-site monitoring server (mainly responsible for centralized data processing, monitoring and unified protocol to facilitate interface compatibility and encryption and decryption of remote transmission), SF6 density micro-water monitoring unit located on each switch body (to realize the gas density, micro-water monitoring unit in the switch body Sampling and data quantification of water and temperature, and complete transmission), a three-in-one integrated intelligent management and diagnosis system is formed for this purpose.
2. On the one hand, the SF6 density micro-water monitoring unit communicates and uploads the collected and quantified SF6 gas density and micro-water content data with the on-site monitoring server through RS485. On the other hand, it will be connected to the relay protection system in the main control room of the substation in the form of passive hard contacts, so that the density and micro-water data of each unit in the switching station can be remotely monitored, and the switching operation trend can be predicted. At the same time, the alarm and blocking protection control of density and sluggish water are linked (users can choose whether they are currently connected or not according to their needs).
3. The on-site monitoring server exchanges data with the host computer or remote computer in the form of power communication protocol or RS485. Realize digital sampling, on-site monitoring, central/main control room monitoring, remote dispatch center synchronous monitoring and management integrated SF6 gas density and micro-water comprehensive online monitoring and status diagnosis system, and regularly output operating status diagnosis report.
Service Guarantee
A. Provide on-site installation, commissioning and training guidance, and carry out on-site demonstration operations.
B. Provide detailed Chinese manual and user guide.
C. One year free warranty, lifetime spare parts support and maintenance.
D. The hotline is available 365 days a day to answer users' inquiries.
Quick Navigation
底部版权
Privacy Statement Terms and Conditions Copyright © Winfoss Seeker Technology (Shanghai) Co., Ltd. All 沪ICP备15031711号 沪公网安备31011802004953号 Power By:www.300.cn